Veridian Light Logo
Veridian
Electrical Equipment Supply · LLC
kVA → FLA → reference feeder size @ 75°C · runs in your browser

Transformer Feeder Sizing Calculator

Transformer kVA and voltage to full-load amps — and a reference secondary feeder size at 75°C ampacity (NEC Table 310.16), with continuous-load margin applied.

Calculator

kVA to feeder size

Reference sizing at 75°C terminations per NEC Table 310.16. Ambient-temperature correction, rooftop ratings, and terminal limits are separate checks — final selection by your engineer of record. Then verify the run length with the voltage drop calculator and the raceway with the conduit fill calculator.

How it works

The math behind the result

Full-load amps
3Ø: FLA = kVA × 1000 ÷ (V × 1.732)  ·  1Ø: FLA = kVA × 1000 ÷ V
Continuous margin
Design current = FLA × 1.25 for loads running ≥ 3 hours (NEC 215.2 / 210.19 basis).
Ampacity table
NEC Table 310.16, 75°C column — matches typical 75°C equipment terminations (NEC 110.14(C)).
Parallel sets
Above ~600 A, paralleling 1/0 AWG+ conductors is standard (identical size, length, routing per NEC 310.10(G)). The tool suggests set counts and per-set sizes.
Not checked here
Ambient correction, temperature derating, raceway fill, and voltage drop — run those separately before finalizing.
FAQ

Common questions

How do you size a transformer secondary feeder?
Start from full-load amps: three-phase FLA = kVA × 1000 ÷ (V × 1.732). Continuous loads (3 hours or more) require conductors at 125% of the continuous current, then select a conductor whose ampacity (NEC Table 310.16, at the termination temperature — typically 75°C) meets the design current. This tool computes the reference size; ambient temperature corrections and terminal ratings are separate checks.
When do I need parallel feeder conductors?
Above roughly 500–600 A, a single conductor becomes impractical and NEC 310.10(G) permits paralleling sizes 1/0 AWG and larger. The tool flags when your design current exceeds the largest single-conductor ampacity and suggests parallel sets — the sets must be identical in size, length, and routing.
Why the 75°C column?
Most modern equipment terminations are rated 75°C, and NEC 110.14(C) limits conductor ampacity to the lowest temperature rating of any termination in the circuit. The 90°C column is used for derating calculations but rarely for final ampacity. Check your gear — older terminals may be 60°C.
Does this account for voltage drop?
No — this is the ampacity check only. Long runs need the voltage-drop check too (3% branch / 5% total reference), which often upsizes the conductor. Run the result through our voltage drop calculator before finalizing.

Need the transformer behind this feeder?

[email protected] · 718-973-0281

The sizing below travels with your request — edit freely.

Your details are used only to prepare your quote. See our Privacy Policy.