Veridian Light Logo
Veridian
Electrical Equipment Supply
37.5kVA · 7200V primary · 120/240V secondary · pad-mount · IEEE C57.12.38

37.5kVA Single-phase Pad-Mount Transformer

7200V primary · 120/240V secondary · pad-mount (liquid-filled)

Configuration

Rated power37.5kVA
PhasesSingle-phase
Primary voltage7200V
Secondary voltage120/240V
MountingPad-mount (liquid-filled)
StandardIEEE C57.12.38
CoolingONAN; Self-Cooled

Primary and secondary voltages, impedance, tap arrangement, fluid and enclosure are all quotable variations on this rating.

Specifications

No-load loss137W
Load loss at 100% (85°C)468W
Total loss at 100%605W
Temperature rise65°C
Taps2 above / 2 below
Sound level48dBA
Dimensions33.86in W x 37.4in D x 25.2in H
FluidMineral oil, non-PCB
Fluid capacity53.78gal

Reference data. These figures describe a comparable published unit, not necessarily the exact unit supplied. The full specification — guaranteed losses, impedance, dimensions and dimensional drawing — is confirmed in your written quote before you commit to an order. Sound levels are NEMA TR-1 maximum limits. Reference losses are not a statement of DOE compliance.

Related units

Nearest ratings in this family

See every rating in the catalog — every rating we list, 15kVA to 4800kVA.

Request pricing

Final losses and dimensions are confirmed in your quote.

Your details are used only to prepare your quote. See our Privacy Policy.