15kVA Single-phase Pole-Mount Transformer
19920V primary · 120/240V secondary · pole-mount (overhead)
Configuration
| Rated power | 15kVA |
|---|---|
| Phases | Single-phase |
| Primary voltage | 19920V |
| Secondary voltage | 120/240V |
| Mounting | Pole-mount (overhead) |
| Standard | IEEE C57.12.20 / C57.12.30 |
| Cooling | ONAN; Self-Cooled |
Primary and secondary voltages, impedance, tap arrangement, fluid and enclosure are all quotable variations on this rating.
Specifications
| No-load loss | 65W |
|---|---|
| Impedance | 1-4.5% |
| Temperature rise | 65°C |
| Taps | 2 above / 2 below |
| Sound level | 48dBA |
| Dimensions | 19.69in W x 22.83in D x 38.19in H |
| Weight, liquid filled | 256lb |
| Fluid | Mineral oil, non-PCB |
Reference data. These figures describe a comparable published unit, not necessarily the exact unit supplied. The full specification — guaranteed losses, impedance, dimensions and dimensional drawing — is confirmed in your written quote before you commit to an order. Sound levels are NEMA TR-1 maximum limits. Reference losses are not a statement of DOE compliance.
Related units
Nearest ratings in this family
See every rating in the catalog — every rating we list, 15kVA to 4800kVA.