100kVA Single-phase Pad-Mount Transformer
7970V primary · 120/240V secondary · pad-mount (liquid-filled)
Configuration
| Rated power | 100kVA |
|---|---|
| Phases | Single-phase |
| Primary voltage | 7970V |
| Secondary voltage | 120/240V |
| Mounting | Pad-mount (liquid-filled) |
| Standard | IEEE C57.12.38 |
| Cooling | KNAN; Self-Cooled |
Primary and secondary voltages, impedance, tap arrangement, fluid and enclosure are all quotable variations on this rating.
Specifications
| No-load loss | 273W |
|---|---|
| Impedance | 1.4-2.4% |
| Temperature rise | 65°C |
| Taps | 2 above / 2 below |
| Sound level | 51dBA |
| Dimensions | 41.34in W x 55.91in D x 37.4in H |
| Fluid | Natural ester or mineral oil |
| Fluid capacity | 102.67gal |
Reference data. These figures describe a comparable published unit, not necessarily the exact unit supplied. The full specification — guaranteed losses, impedance, dimensions and dimensional drawing — is confirmed in your written quote before you commit to an order. Sound levels are NEMA TR-1 maximum limits. Reference losses are not a statement of DOE compliance.
Related units
Nearest ratings in this family
See every rating in the catalog — every rating we list, 15kVA to 4800kVA.